The AJ65SBTB2N-8S and AJ65SBTB2N-16S are Mitsubishi CC-Link remote I/O modules engineered for demanding AC output applications. These modules provide reliable switching of 100–240 VAC loads with photocoupler isolation, ensuring galvanic separation between the CC-Link network and field devices. With a maximum load current of 0.6 A per point and robust surge suppression, they are ideally suited for controlling contactors, valves, and lighting systems in industrial automation. The modules occupy a single station with 32-point assignment, simplifying network configuration. Below are the comprehensive technical specifications.
| Parameter | AJ65SBTB2N-8S | AJ65SBTB2N-16S |
|---|---|---|
| Number of Output Points | 8 points | 16 points |
| Insulation Method | Photocoupler | Photocoupler |
| Rated Load Voltage | 100 to 240 V AC 50/60 Hz ±5% | 100 to 240 V AC 50/60 Hz ±5% |
| Max. Load Voltage | 264 V AC | 264 V AC |
| Max. Load Current | 0.6 A/point, 2.4 A/1 common | 0.6 A/point, 4.8 A/1 common |
| Min. Load Voltage × Current | 50 V AC 100 mA, 100 V AC 10 mA, 240 V AC 10 mA | 50 V AC 100 mA, 100 V AC 10 mA, 240 V AC 10 mA |
| Max. Inrush Current | 25 A 10 ms or lower | 25 A 10 ms or lower |
| Leakage Current at OFF | 1.5 mA rms or lower (100 V AC rms 60 Hz), 3 mA rms or lower (200 V AC rms 60 Hz) | 1.5 mA rms or lower (100 V AC rms 60 Hz), 3 mA rms or lower (200 V AC rms 60 Hz) |
| Max. Voltage Drop at ON | 1.5 V rms or lower (at 0.6 A) | 1.5 V rms or lower (at 0.6 A) |
| Surge Suppression | C·R absorber (0.01 μF + 47 Ω) | C·R absorber (0.01 μF + 47 Ω) |
| Common Method | 8 points/1 common (terminal block 2-wire type) | 16 points/1 common (terminal block 2-wire type) |
| Number of Stations Occupied | 1 station, 32 points assignment (use 8 points) | 1 station, 32 points assignment (use 16 points) |
| Noise Durability | Simulator noise 1500 Vp-p, noise width 1 ms, carrier frequency 25 to 60 Hz; Fast transient/burst IEC61000-4-4: 1 kV | Simulator noise 1500 Vp-p, noise width 1 ms, carrier frequency 25 to 60 Hz; Fast transient/burst IEC61000-4-4: 1 kV |
| Withstand Voltage | 2830 V AC between all AC external terminals and ground, rms/3 cycles (2000 m above sea level); 500 V AC for 1 minute between all DC external terminals and ground | 2830 V AC between all AC external terminals and ground, rms/3 cycles (2000 m above sea level); 500 V AC for 1 minute between all DC external terminals and ground |
| Insulation Resistance | 10 MΩ or higher, measured with 500 V DC insulation tester between all AC/DC external terminals and ground | 10 MΩ or higher, measured with 500 V DC insulation tester between all AC/DC external terminals and ground |
| Weight | 0.25 kg (0.55 lb) | 0.35 kg (0.77 lb) |
| External Connection Method | 7-point 2-piece terminal block (transmission circuit, module power supply); Direct-type 18-point terminal block (I/O power supply area) (M3 screw) | 7-point 2-piece terminal block (transmission circuit, module power supply); Direct-type 34-point terminal block (I/O power supply area) (M3 screw) |
| Applicable Solderless Terminal | RAV1.25-3.5 (JIS C 2805) [Wire: 0.3–1.25 mm²]; V2-MS3, RAP2-3S, RAP2-3; 2-3N, 2-3S [Wire: 1.25–2 mm²] | RAV1.25-3.5 (JIS C 2805) [Wire: 0.3–1.25 mm²]; V2-MS3, RAP2-3S, RAP2-3; 2-3N, 2-3S [Wire: 1.25–2 mm²] |