The DELTA PLC CONTROLLER AH SERIES REDUNDANT CPU is a high-performance, modular programmable logic controller designed for advanced automation systems requiring fault tolerance and uninterrupted operation. This CPU module, part of the Delta AH series, integrates a redundant architecture that automatically switches control in the event of a primary unit failure, making it ideal for critical processes in manufacturing, energy, and infrastructure. With IEC 61131-3 compliance, it supports multiple programming languages including Ladder Diagram (LD), Continuous Function Chart (CFC), Structured Text (ST), and Sequential Function Chart (SFC). The unit features a cyclic execution model with direct I/O refresh capabilities, ensuring deterministic response times. Its robust hardware includes DIN rail or screw mounting, backplane-based module installation, and a wide range of built-in communication interfaces for seamless integration into existing networks.
| Parameter | Specification | Remarks |
|---|---|---|
| Execution Method | Cyclic program execution | - |
| I/O Control | Cyclically refreshed inputs/outputs; Direct inputs/outputs (DX/DY devices) | DX/DY allow direct I/O control |
| Programming Language | IEC 61131-3 (LD, CFC, ST, SFC) | - |
| Instruction Execution Speed | 0.3 ms/K steps | - |
| Constant Scan Cycle (ms) | 1–32000 (adjustable in 1 ms increments) | Configurable via parameters |
| Program Capacity | 256K steps | - |
| Installation | DIN rails or screws | - |
| Module Installation | Directly on a backplane | - |
| Max Modules per Backplane | 5 I/O modules (motion backplane) | - |
| Number of Tasks | 283 total: 32 cyclic, 32 I/O interrupt, 212 external interrupt, 1 24V LV detection, 4 timed interrupt, 2 communication interrupt | - |
| I/O Devices (Bit) | 8192 (X0.0–X511.15 / Y0.0–Y511.15) | Program-accessible |
| I/O Devices (Word) | 512 (X0–X511 / Y0–Y511) | - |
| Max I/O Points (CPU) | 338 inputs / 324 outputs (with AHBP05M2-5A backplane) | - |
| Input Relay [X] | 8192 (X0.0–X511.15) | - |
| Output Relay [Y] | 8192 (Y0.0–Y511.15) | - |
| Auxiliary Relay [M] | 8192 (M0–M8191) | - |
| Timer [T] | 2048 (T0–T2047) | - |
| Counter [C] | 2048 (C0–C2047) | - |
| 32-bit Counter [HC/AC] | HC: 64 (HC0–HC63); AC: 56 (AC0–AC55) | - |
| Data Register [D] | Bit: 1,048,576 (D0.0–D65535.15); Word: 65536 (D0–D65535) | - |
| Stepping Relay [S] | 2048 (bit) (S0–S2047) | - |
| Index Register [E] | 32 (word) (E0–E31) | - |
| Special Auxiliary Relay [SM] | 2048 (bit) (SM0–SM2047) | - |
| Special Data Register [SR] | 2048 (word) (SR0–SR2047) | - |
| Serial Communication Ports | 1 x RS-232 (USB), 1 x RS-485 | - |
| Ethernet Port | 10/100 M | - |