VFD25AMS43ANSAA Procurement Questions
Which motor rating and output current can this drive handle?
The drive is rated for an applicable motor output of 11 kW (15 HP), with a rated output current of 25 A heavy duty / 28 A normal duty. Overload tolerance is ND 120% 60 s / 150% 3 s and HD 150% 60 s / 200% 3 s, so the duty class you select determines the continuous current you can draw.
What supply voltage and frequency does this model require?
It is rated for three-phase AC 380 to 480 V (-15% to +10%), 50/60 Hz, with a mains input voltage range of 323 to 528 V. Confirm your site supply falls inside that window before ordering.
Is an EMC filter built into the VFD25AMS43ANSAA?
No. This model (ANSAA) has no built-in EMC filter. The protection rating is IP20 (standard model), so plan the enclosure and any external EMC measures accordingly.
Does it have a brake chopper, and what communications and safety functions are available?
A brake chopper is built in, and a DC reactor is optional. Communications: built-in RS-485 Modbus, with optional PROFIBUS DP / DeviceNet / Modbus TCP / EtherNet/IP / CANopen / EtherCAT cards. An integrated Safe Torque Off (STO) safety function is included.
What are the physical dimensions and frame size for panel layout?
The drive measures 130.0 x 250.0 x 185.0 mm (W x H x D). The frame size is Frame E (dimensions sub-frame E1), so use those figures when checking panel space, clearances and mounting hole positions.
- Applicable motor output
- 11 kW (15 HP)
- Rated output current (HD / ND)
- 25 A heavy duty / 28 A normal duty
- Frame size
- Frame E (dimensions sub-frame E1)
- Rated voltage and frequency
- Three-phase AC 380 to 480 V (-15% to +10%), 50/60 Hz
- Mains input voltage range
- 323 to 528 V
- Brake chopper
- Built-in brake chopper; DC reactor optional
- Maximum output frequency
- 599.00 Hz (standard model)
- Overload tolerance
- ND 120% 60 s / 150% 3 s; HD 150% 60 s / 200% 3 s
- Communications
- Built-in RS-485 Modbus; optional PROFIBUS DP / DeviceNet / Modbus TCP / EtherNet/IP / CANopen / EtherCAT cards
- Safety function
- Integrated Safe Torque Off (STO)
- EMC filter
- No built-in EMC filter (ANSAA)
- Protection rating
- IP20 (standard model)
- Dimensions
- 130.0 x 250.0 x 185.0 mm (W x H x D)
- Delta MS300 Series catalogue (via Mouser) — MS300 catalogue, ordering information (460V/3-phase)
- Delta MS300 Series catalogue, specifications — MS300 catalogue, specifications (3-phase 460 V)
- Delta MS300 Series catalogue, ordering information — MS300 catalogue, ordering information (460V/3-phase)
- Delta MS300 Series catalogue, general specifications — MS300 catalogue, general specifications
- Delta MS300 Series catalogue, features — MS300 catalogue, features
- Delta MS300 Series catalogue, models overview — MS300 catalogue, models overview
- Delta MS300 Series catalogue, dimensions — MS300 catalogue, Dimensions - IP20/IP40 (Frame E1)
Technical specifications are based on the linked manufacturer references.
What Does Our Clients Say
Mitsubishi MR-J4
Laura Navas
Great product!
2019/12/01
Keyence sensor
EQDR SALES
Original and fast!
2020/02/22